[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933066":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933066,604,1,"单选题","某4层地上商店建筑，每层建筑面积为8500m2，所设置的湿式自动喷水灭火系统共使用了2960只闭式喷头，该系统应设置（ ）个末端试水装置。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2",false,{"key":16,"text":17,"correct":14},"B","3",{"key":19,"text":20,"correct":21},"C","4",true,{"key":23,"text":24,"correct":14},"D","5","《自动喷水灭火系统设计规范》（GB 50084-2017），6.2.3，一个湿式报警阀组控制的喷头数不宜超过800只，因此该系统共需设置2960÷800=3.7，向上取整为4个。每个报警阀组控制的最不利点喷头处，应设置末端试水装置。因此4个报警阀组应设置4个末端试水装置。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]