[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933060":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933060,604,1,"单选题","某印刷厂，火灾危险等级为严重Ⅰ级，设湿式自动喷水灭火系统全保护，则配水支管控制的喷头数量最多为（ ）个。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","9",false,{"key":16,"text":17,"correct":14},"B","10",{"key":19,"text":20,"correct":14},"C","8",{"key":22,"text":23,"correct":24},"D","6",true,"根据《自动喷水灭火系统设计规范》 GB50084-2017——8.0.8，配水管两侧每根配水支管控制的标准流量洒水喷头数量，轻危险级、中危险级场所不应超过8只，同时在吊顶上下设置喷头的配水支管，上下侧均不应超过8只。严重危险级及仓库险级场所均不应超过6只。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]