[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933058":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},933058,604,1,"单选题","下列场所设置自动喷水灭火系统进行保护，在进行喷头选型时，做法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","某未做吊项的场所，设置湿式系统保护，配水支管布置在梁下，采用了下垂型喷头",true,{"key":16,"text":17,"correct":18},"B","某设置吊顶的场所，设置湿式系统保护，在吊顶下布置喷头，采用了下垂型喷头",false,{"key":20,"text":21,"correct":18},"C","某顶板为水平面的单位办公楼，设置湿式系统保护，办公室采用了边墙型喷头",{"key":23,"text":24,"correct":18},"D","某工厂设备间，设置预作用系统保护，采用了干式下垂型喷头","《自动喷水灭火系统设计规范》（GB 50084-2005），6.1.3，湿式系统的喷头造型应符合下列规定： 1、不做吊顶的场所，当配水支管布置在梁下时，应采用直立型喷头； 2、吊顶下布置的喷头，应采用下垂型喷头或吊顶型喷头； 3、顶板为水平面的轻危险级、中危险级Ⅰ级居室和办公室，可采用边墙型喷头； 4、自动喷水一泡沫联用系统应采用洒水喷头； 5、易受碰撞的部位，应采用带保护罩的喷头或吊顶型喷头。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]