[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933055":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933055,604,1,"单选题","关于末端试水装置设置的说法，错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","末端试水装置和试水阀应设在便于操作的部位",false,{"key":16,"text":17,"correct":14},"B","每个报警阀组控制的最不利点喷头处应设置末端试水装置",{"key":19,"text":20,"correct":14},"C","末端试水装置的出水，应采用孔口出流的方式排入排水管道",{"key":22,"text":23,"correct":24},"D","末端试水装置出水口的流量数，应大于与系统同楼层选用的喷头数",true,"根据《自动喷水灭火系统设计规范》（GB50084—2017）中6．5．1，每个报警阀组控制的最不利点洒水喷头处应设末端试水装置，其他防火分区、楼层均应设直径为25mm的试水阀。B正确。 根据6.5.2，末端试水装置应由试水阀、压力表以及试水接头组成。试水接头出水口的流量系数，应等同于同楼层或防火分区内的最小流量系数洒水喷头。末端试水装置的出水，应采取孔口出流的方式排入排水管道，排水立管宜设伸顶通气管，且管径不应小于75mm。C正确，D错误。 因此本题选择D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]