[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933054":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},933054,604,1,"单选题","某耐火等级为二级的6层建筑，高度为28m，每层建筑面积为12000m2，首层设有净空高度为6．2m的商店营业厅。建筑内全部采用不燃或难燃材料进行装修，并设置了湿式自动喷水灭火系统和火灾自动报警系统保护，该商店营业厅内至少应设置（ ）个水流指示器。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","20",false,{"key":16,"text":17,"correct":18},"B","3",true,{"key":20,"text":21,"correct":14},"C","4",{"key":23,"text":24,"correct":14},"D","18","除报警阀组控制的喷头只保护不超过防火分区面积的同层场所外，每个防火分区、每个楼层均应设水流指示器；根据题意，该商场一个防火分区的最大允许建筑面积为4000m2，该商场6层，每层至少应划分为3个防火分区，故首层至少应设置3个水流指示器。 “题中只有首层是商店营业厅，问题也是商业营业厅应该设置多少个水流指示器”",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]