[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933052":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},933052,604,1,"单选题","下列有关末端试水装置的说法中，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","试水接头出水口的流量系数，应等同于同楼层或防火分区内的最大流量系数喷头",false,{"key":16,"text":17,"correct":14},"B","末端试水装置应由试水阀、压力表、水流指示器以及试水接头组成",{"key":19,"text":20,"correct":21},"C","每个报警阀组控制的最不利点喷头处应设末端试水装置",true,{"key":23,"text":24,"correct":14},"D","末端试水装置连接管的管径不应小于20mm","根据《自动喷水灭火系统设计规范》GB50084—20176．5．2，末端试水装置应由试水阀、压力表以及试水接头组成，试水接头出水口的流量系数，应等同于同楼层或防火分区内的最小流量系数洒水喷头，AB选项错误；根据6．5．1，每个报警阀组控制的最不利点喷头处应设末端试水装置，其他防火分区、楼层均应设直径为25mm的试水阀，C选项正确；根据8．0．10，短立管及末端试水装置的连接管，其管径不应小于25mm，D选项错误。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]