[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933048":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},933048,604,1,"单选题","下列不属于防护冷却系统和防护冷却水幕系统不同之处的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","使用的喷头类型不同",false,{"key":16,"text":17,"correct":14},"B","防护冷却系统是闭式系统，防护冷却水幕系统是开式系统",{"key":19,"text":20,"correct":14},"C","喷头最大设置点高度不同",{"key":22,"text":23,"correct":24},"D","持续喷水时间都与被保护部位的耐火极限有关",true,"根据《自动喷水灭火系统设计规范》GB50084—20172．1．11，防护冷却水幕是指由水幕喷头、雨淋报警阀组或感温雨淋报警阀等组成，发生火灾时用于冷却防火卷帘、防火玻璃墙等防火分割设施的水幕系统；根据2．1．12，防护冷却系统是指由闭式洒水喷头、湿式报警阀组等组成，发生火灾时用于冷却防火卷帘、防火玻璃墙等防火分隔设施的闭式系统，AB选项属于两者的不同之处；根据5．0．14，防护冷却水幕系统喷头的设置点高度可以大于8m；根据5．0．15，防护冷却系统喷头设置点高度不应超过8m，C选项属于两者的不同之处； 根据5．1．14—3、5．0．15—4，持续喷水时间均不应小于系统设置部位的耐火极限要求，D选项是两者的相同之处，D选项正确。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]