[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933044":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933044,604,2,"多选题","对于采用充液传动管直接控制的雨淋系统，可以直接自动启动消防水泵的是（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","感烟火灾探测器",false,{"key":16,"text":17,"correct":18},"B","高位水箱出水管上设置的流量开关",true,{"key":20,"text":21,"correct":18},"C","消防水泵出水干管上设置的压力开关",{"key":23,"text":24,"correct":14},"D","水流指示器",{"key":26,"text":27,"correct":18},"E","雨淋报警阀组上设置的压力开关","BCE","根据《自动喷水灭火系统设计规范》GB50084—201711．0．3，雨淋系统的消防水泵的自动启动方式应符合下列要求：当采用充液（水）传动管控制雨淋报警阀时，消防水泵应由消防水泵出水干管上设置的压力开关、高位消防水箱出水管上的流量开关和报警阀组压力开关直接启动。本题答案为BCE。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]