[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933043":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933043,604,2,"多选题","下列关于自动喷水灭火系统报警阀组的说法，错误的是（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","报警阀组设置在专用的报警阀室，设置点的环境温度为0℃",true,{"key":16,"text":17,"correct":14},"B","某建筑高度60m，地下一层，地上20层，每层均设置自动喷水灭火系统，一个报警阀组设置在地下一层",{"key":19,"text":20,"correct":21},"C","水幕系统应设置独立的报警阀组或感温雨淋阀",false,{"key":23,"text":24,"correct":21},"D","当闭式系统保护室内钢屋架时，应单独设置独立报警阀组，不可合用",{"key":26,"text":27,"correct":14},"E","某货架仓库设置自动喷水灭火系统，顶板下喷头与货架内共设置一个水流指示器","ABE","A错，报警阀组宜设在安全且易于操作、检修的地点，环境温度不低于4℃且不高于70℃；B错，每个报警阀组供水的最高和最低位置喷头的高程差不宜大于50m；E错，仓库内顶板下喷头与货架内喷头应分别设置水流指示器。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]