[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-933038":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},933038,604,2,"多选题","某综合楼设置了湿式自动喷水灭火系统进行保护，系统采用直立型喷头，下列关于喷头安装的说法中，符合现行国家消防技术标准的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","无梁或其他障碍物时，溅水盘与顶板的距离，不应小于75mm，不应大于150mm",true,{"key":16,"text":17,"correct":18},"B","有梁或其他障碍物时，溅水盘与顶板的距离，不应大于250mm",false,{"key":20,"text":21,"correct":14},"C","当在梁或其他障碍物底面下方的平面上布置洒水喷头时，溅水盘与顶板的距离不应大于300mm，同时溅水盘与梁等障碍物底面的垂直距离应为25mm~100mm",{"key":23,"text":24,"correct":18},"D","密肋梁板下方的喷头，溅水盘与密肋梁板底面的垂直距离，不应小于50mm，不应大于100mm",{"key":26,"text":27,"correct":14},"E","在梁间布置的喷头，确有困难时，溅水盘与顶板的距离，不应大于550mm","ACE","《自动喷水灭火系统设计规范》（GB 50084-2017）,7.1.3,选项B，不应大于300mm。选项D，不应小于25mm，不应大于100mm。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]