[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932990":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932990,604,2,"多选题","某图书馆建筑，建筑高度为18m，屋面板的耐火极限为1．5h，对图书馆的外墙进行保温设计，下列不符合规范要求的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","采用外墙内保温时，建筑内疏散楼梯使用燃烧性能为B1级的保温材料",true,{"key":16,"text":17,"correct":18},"B","保温材料的防护层使用不燃烧材料",false,{"key":20,"text":21,"correct":14},"C","采用外墙外保温时，使用燃烧性能为B1级的保温材料",{"key":23,"text":24,"correct":18},"D","对建筑的外墙装饰层，采用燃烧性能为B1级的材料",{"key":26,"text":27,"correct":18},"E","建筑屋面的外保温系统，使用燃烧性能为B2级的保温材料","AC","A错，对于人员密集场所，用火、燃油、燃气等具有火灾危险性的场所以及各类建筑内的疏散楼梯间、避难走道、避难间、避难层等场所或部位，应采用燃烧性能A级的保温材料。C错，设置人员密集场所的建筑，其外墙外保温材料的燃烧性能应为A级。D正确，建筑外墙的装饰层应采用燃烧性能为A级的材料，若建筑高度不大于50m，可采用B1级材料。E正确，建筑的屋面外保温系统，当屋面板的耐火极限不低于1．00h时，保温材料的燃烧性能不应低于B2级。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]