[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932942":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932942,604,2,"多选题","某综合楼，建筑高度58m，设置防排烟系统、自动喷水灭火系统、火灾自动报警系统保护，下列建筑内通风空调系统中的部位需要设置防火阀的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","防火分区处",true,{"key":16,"text":17,"correct":14},"B","变形缝两侧",{"key":19,"text":20,"correct":21},"C","办公室防火隔墙处",false,{"key":23,"text":24,"correct":14},"D","排烟机房处",{"key":26,"text":27,"correct":21},"E","竖向风管与每层水平风管交接处的竖向管段上","ABD","根据《建筑设计防火规范》GB 50016—2014（2018年版）9．3．11，通风、空气调节系统的风管在下列部位应设置公称动作温度为70℃的防火阀： 1）穿越防火分区处。 2）穿越通风、空气机房的房间隔墙和楼板处。 3）穿越重要或火灾危险性大的场所的房间隔墙和楼板处。 4）穿越防火分隔处的变形缝两侧。 5）竖向风管与每层水平风管交接处的水平管段上。 注：当建筑内每个防火分区的通风、空气调节系统均独立设置时，水平风管与竖向总管的交接处可不设置防火阀。 本题答案为ABD。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]