[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932941":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932941,604,1,"单选题","净化有爆炸危险粉尘的干式除尘器和过滤器宜布置在厂房外的独立建筑内，建筑外墙与所属厂房的防火间距不应小于（ ）m。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","10",true,{"key":16,"text":17,"correct":18},"B","15",false,{"key":20,"text":21,"correct":18},"C","30",{"key":23,"text":24,"correct":18},"D","40","净化有爆炸危险粉尘的干式除尘器和过滤器宜布置在厂房外的独立建筑内，建筑外墙与所属厂房的防火间距不应小于10m，以免粉尘一旦爆炸波及厂房扩大灾害损失。 符合下列条件之一的干式除尘器和过滤器，可布置在厂房的单独房间内，但应采用耐火极限分别不低于3.00h 的防火隔墙和耐火极限不低于1.50 h的楼板与其他部位分隔 。 1.有连续清尘设备的除尘器和过滤器。 2.风量不超过15000m3／h、集尘斗的储尘量小于60kg的定期清灰的除尘器和过滤器。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]