[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932937":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932937,604,1,"单选题","关于净化有爆炸危险粉尘的干式除尘器和过滤器的设置，做法错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","布置在厂房之外的独立建筑内",false,{"key":16,"text":17,"correct":14},"B","与所属厂房的防火间距为10m",{"key":19,"text":20,"correct":14},"C","有连续清尘设备可布置在厂房的单独房间内，但应采用耐火极限分别不低于3．00h的防火隔墙和1．50h的楼板与其他部位分隔",{"key":22,"text":23,"correct":24},"D","风量20000m3／h，且集尘斗的储尘量50kg的定期清灰的除尘器和过滤器，可布置在厂房的单独房间内，但应采用耐火极限分别不低于3．00h的隔墙和1．50h的楼板与其他部位分隔",true,"符合下列条件之一的干式除尘器和过滤器，可布置在厂房的单独房间内，但应采用耐火极限分别不低于 3.00h 的防火隔墙和耐火极限不低于1.50 h的楼板与其他部位分隔 。 1）有连续清尘设备的除尘器和过滤器。 2） 风量不超过15000m3\u002Fh，且集尘斗的储尘量小于60Kg的定期清灰的除尘器和过滤器 。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]