[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932935":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932935,604,1,"单选题","某公共建筑地上10层，建筑面积6000m2。燃气锅炉房采用机械通风，该风机正常排风换气次数应不少于（ ）次／h。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","12",false,{"key":16,"text":17,"correct":18},"B","6",true,{"key":20,"text":21,"correct":14},"C","3",{"key":23,"text":24,"correct":14},"D","8","根据《建筑设计防火规范》GB 50016—2014（2018年版）9．3．16，燃油或燃气锅炉房应设置自然通风或机械通风设施。燃气锅炉房应选用防爆型的事故排风机。当采取机械通风时，机械通风设施应设置导除静电的接地装置，通风量应符合下列规定：1）燃油锅炉房的正常通风量应按换气次数不少于3次／h确定，事故排风量应按换气次数不少于6次／h确定；2）燃气锅炉房的正常通风量应按换气次数不少于6次／h确定，事故排风量应按换气次数不少于12次／h确定。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]