[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932924":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932924,604,1,"单选题","通风、空气调节系统的风管在穿越通风、空气调节机房的房间隔墙和楼板处应设置公称动作温度为（ ）℃的防火阀。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","70",true,{"key":16,"text":17,"correct":18},"B","80",false,{"key":20,"text":21,"correct":18},"C","100",{"key":23,"text":24,"correct":18},"D","120","根据《建筑设计防火规范》GB50016—2014 （2018版） 第9．3．11条规定，通风、空气调节系统的风管在下列部位应设置公称动作温度为70℃的防火阀：（1）穿越防火分区处；（2）穿越通风、空气调节机房的房间隔墙和楼板处；（3）穿越重要或火灾危险性大的场所的房间隔墙和楼板处；（4）穿越防火分隔处的变形缝两侧；（5）竖向风管与每层水平风管交接处的水平管段上。注：当建筑内每个防火分区的通风、空气调节系统均独立设置时，水平风管与竖向总管的交接处可不设置防火阀。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]