[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932918":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932918,604,1,"单选题","下列关于布置在建筑内的柴油发电机房的防火设计做法，不正确的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","柴油发电机房内设有储油间，其总储存量为0．5m3",false,{"key":16,"text":17,"correct":14},"B","柴油发电机房的储油间采用耐火极限为3．00h的防火隔墙与发电机间分隔，隔墙上开甲级防火门",{"key":19,"text":20,"correct":21},"C","柴油发电机房设置有火灾报警装置，并采用耐火极限为2．50h的防火隔墙和1．50h的不燃性楼板与其他部位分隔，连通处采用乙级防火门",true,{"key":23,"text":24,"correct":14},"D","柴油发电机房储油间的油箱密闭且设置有通向室外的通气管，通气管设置有带阻火器的呼吸阀","根据《建筑设计防火规范》GB50016—2014（2018年版）5．4．13—4，柴油发电机房内设置储油间时，其总储存量不应大于1m3，储油间应采用耐火极限不低于3．00h的防火隔墙与发电机间分隔；确需在防火隔墙上开门时，应设置甲级防火门，AB选项正确：根据5．4．13—3，布置在民用建筑内的柴油发电机房应采用耐火极限不低于2．00h的防火隔墙和1．50h的不燃性楼板与其他部位分隔，门应采用甲级防火门，C选项错误；根据。5．4．15—2，柴油发电机房储油间的油箱应密闭且应设置通向室外的通气管，通气管应设置带阻火器的呼吸阀，油箱的下部应设置防止油品流散的设施，D选项正确。本题答案为C",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]