[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932916":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932916,604,1,"单选题","下列关于电力变压器的防火防爆措施检查，不符合规范要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","油浸变压器室、高压配电装置室的耐火等级为二级",false,{"key":16,"text":17,"correct":14},"B","10kV及以下的预装式变电站与民用建筑的防火间距为5．00m",{"key":19,"text":20,"correct":21},"C","油浸电力变压器布置在民用建筑内时，变压器室与其他部位之间应采用耐火极限不低于2．00h的不燃性隔墙和1．00h的不燃性楼板隔开",true,{"key":23,"text":24,"correct":14},"D","油浸电力变压器布置在民用建筑内时，变压器室与配电室之间，应采用耐火极限不低于2．00h的防火隔墙隔开","油浸电力变压器布置在民用建筑内时，变压器室与其他部位之间应采用耐火极限不低于2．00h的防火隔墙和1．50h的不燃性楼板隔开。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]