[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932914":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932914,604,1,"单选题","燃油或燃气锅炉房采用机械通风设施时，该机械通风设备应设置导除静电的接地装置。下列关于通风量的确定，不符合规定的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","燃油锅炉房的正常通风量按换气次数4次／h确定",false,{"key":16,"text":17,"correct":14},"B","燃油锅炉房的事故排风量按换气次数7次／h确定",{"key":19,"text":20,"correct":14},"C","燃气锅炉房的正常通风量按换气次数7次／h确定",{"key":22,"text":23,"correct":24},"D","燃气锅炉房的事故排风量按换气次数9次／h确定",true,"燃油或燃气锅炉房可采用自然通风或机械通风，当设置机械通风设施时，该机械通风设备应设置导除静电的接地装置，通风量应符合下列规定: 1 ）燃油锅炉房的正常通风量按换气次数不少于3次\u002Fh确定，事故排风量应按换气次数不少于6次\u002Fh确定。 2） 燃气锅炉房的正常通风量按换气次数不少于6次\u002Fh确定，事故排风量应按换气次数不少于12次\u002Fh确定。 本题答案是D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]