[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932909":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932909,604,1,"单选题","下列关于干式除尘器设置的说法，不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","净化有爆炸危险粉尘的干式除尘器和过滤器宜布置在厂房外的独立建筑内，建筑外墙与所属厂房的防火间距不应小于10m",false,{"key":16,"text":17,"correct":14},"B","具备连续清灰功能干式除尘器的设备房布置在厂房内时，采用耐火极限3．00h的防火隔墙和1．50h的楼板与其他部位分隔",{"key":19,"text":20,"correct":14},"C","净化有爆炸危险粉尘和碎屑的除尘器均应设置泄压装置",{"key":22,"text":23,"correct":24},"D","净化有爆炸危险粉尘的干式除尘器应布置在系统的正压段上",true,"根据《建筑设计防火规范》GB 50016—2014（2018年版）9．3．7，净化有爆炸危险粉尘的干式除尘器和过滤器宜布置在厂房外的独立建筑内，建筑外墙与所属厂房的防火间距不应小于10m，A选项正确；具备连续清灰功能，或具有定期清灰功能且风量不大于15000m3／h、集尘斗的储尘量小于60kg的干式除尘器和过滤器，可布置在厂房内的单独房间内，但应采用耐火极限不低于3．00h的防火隔墙和1．50h的楼板与其他部位分隔，B选项正确；根据9．3．8，净化或输送有爆炸危险粉尘和碎屑的除尘器、过滤器或管道，均应设置泄压装置；净化有爆炸危险粉尘的干式除尘器和过滤器应布置在系统的负压段上，C选项正确，D选项错误。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]