[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932819":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932819,604,1,"单选题","某二级耐火等级的展览厅，地上3层，每层建筑面积2500m2，采用自动喷水灭火系统、火灾自动报警系统保护，每层在建筑两侧均设有安全出口，则该展览厅室内任意一点到最近安全出口的直线距离不应大于（ ）m。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","10",false,{"key":16,"text":17,"correct":14},"B","30",{"key":19,"text":20,"correct":14},"C","40",{"key":22,"text":23,"correct":24},"D","50",true,"根据《建筑设计防火规范》GB 50016—2014（2018年版）5．5．17—4，一、二级耐火等级建筑内疏散门或安全出口不少于2个的观众厅、展览厅、多功能厅、餐厅、营业厅等。其室内任一点至最近疏散门或安全出口的直线距离不应大于30m；当疏散门不能直通室外地面或疏散楼梯间时，应采用长度不大于10m的疏散走道通至最近的安全出口。当该场所设置自动喷水灭火系统时，室内任一点至最近安全出口的安全疏散距离可分别增加25％，30×（1+0．25）+10×（1+0．25）=50m。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]