[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932814":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932814,604,1,"单选题","某一级耐火等级综合楼，地上4层，地下2层，层高4m，首层设计疏散人数为800人，地下一层设计疏散人数为1200人，地下二层设计疏散人数为1500人，则地下一层到首层疏散楼梯的最小疏散总净宽度不应小于（ ）m。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","11．25",true,{"key":16,"text":17,"correct":18},"B","9．0",false,{"key":20,"text":21,"correct":18},"C","15",{"key":23,"text":24,"correct":18},"D","12","根据《建筑设计防火规范》GB 50016—2014（2018年版）5．5．21，除剧场、电影院、礼堂、体育馆外的其他公共建筑，其房间疏散门、安全出口、疏散走道和疏散楼梯的各自总净宽度，应符合下列规定：每层的房间疏散门、安全出口、疏散走道和疏散楼梯的各自总净宽度，应根据疏散人数按每100人的最小疏散净宽度不小于表5．5．21—1的规定计算确定。当每层疏散人数不等时，疏散楼梯的总净宽度可分层计算，地上建筑内下层楼梯的总净宽度应按该层及以上疏散人数最多一层的人数计算；地下建筑内上层楼梯的总净宽度应按该层及以下疏散人数最多一层的人数计算。根据题意1500×0．75=11．25m，1200×0．75=9．0m。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]