[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932786":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932786,604,1,"单选题","某单位一栋5层办公楼，总建筑面积为4500m2，采用采用敞开式外廊，楼内设置了送回风道（管）的集中空气调节系统，并按照消防要求设置了自动喷水灭火系统。其位于两个安全出口之间的房间疏散门至最近安全出口的疏散距离不应大于（ ）m。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","40",false,{"key":16,"text":17,"correct":14},"B","45",{"key":19,"text":20,"correct":21},"C","55",true,{"key":23,"text":24,"correct":14},"D","37.5","根据《建筑设计防火规范》GB50016—2014（2018年版）5.5.17，条文说明：本表的注是针对各种情况对表中规定值的调整，对于一座全部设置自动喷水灭火系统的建筑，且符合注1或注2的要求时，其疏散距离是按照注3的规定增加后，再进行增减。40×（1+25%）+5=55m。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]