[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932785":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932785,604,1,"单选题","下列关于避难走道的设置，不符合规范要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","避难走道楼板的耐火极限不应低于1．50h",false,{"key":16,"text":17,"correct":18},"B","避难走道内部装修材料的燃烧性能不应低于B1级",true,{"key":20,"text":21,"correct":14},"C","避难走道直通地面的出口不应少于2个，并应设置在不同方向",{"key":23,"text":24,"correct":14},"D","避难防火分区至避难走道入口处应设置防烟前室，前室的使用面积8．0m2","避难走道内部装修材料的燃烧性能应为A级；D正确，避难防火分区至避难走道入口处应设置防烟前室，前室的使用面积不应小于6．0m2（最小需要6.0㎡，大于规范要求是没有错的）。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]