[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932778":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932778,604,1,"单选题","大型地下商场，总建筑面积为21000m2，则该建筑内消防应急照明备用电源的连续供电时间不应低于（ ）min。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","30",false,{"key":16,"text":17,"correct":18},"B","60",true,{"key":20,"text":21,"correct":14},"C","120",{"key":23,"text":24,"correct":14},"D","180","根据《建筑设计防火规范》GB50016—2014（2018年版）10．1．5： 建筑内消防应急照明和灯光疏散指示标志的备用电源的连续供电时间应符合下列规定： 1 建筑高度大于100m 的民用建筑，不应小于1.5h； 2 医疗建筑、老年人照料设施、总建筑面积大于100000m2的公共建筑和总建筑面积大于20000m2的地下、半地下建筑，不应少于1.0h； 3 其他建筑，不应少于0.5h。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]