[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932729":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932729,604,2,"多选题","下列关于建筑内消防应急照明灯具照度的说法中，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","商场疏散走道的地面最低水平照度不应低于1．0lx",false,{"key":16,"text":17,"correct":18},"B","避难走道地面最低水平照度不应低于5．0lx",true,{"key":20,"text":21,"correct":14},"C","避难层（间）的地面最低水平照度不应低于5．0lx",{"key":23,"text":24,"correct":18},"D","手术部的避难间地面最低水平照度不应低于10．0lx",{"key":26,"text":27,"correct":18},"E","普通办公楼楼梯间的地面最低水平照度不应低于5．0lx","BDE","（1）建筑内消防应急照明灯具的照度应符合下列规定: 1）疏散走道的地面最低水平照度不应低于1.0lx. 2）人员密集场所、避难层（间）内的地面最低水平照度不应低于3.01x; 对于病房楼或手术部的避难间，不应低于10.0lx 。 3）楼梯间、前室或合用前室、避难走道的地面最低水平照度不应低于5.0lx. 4） 消防控制室、消防水泵房、自备发电机房、配电室、防烟与排烟机房，以及发生火灾时仍需正常工作的其他房间的消防应急照明，仍应保证正常照明的照度。 （2）消防应急照明灯具宜设置在墙面的上部、顶棚上或出口的顶部。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]