[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932713":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932713,604,1,"单选题","某二级耐火等级的面粉加工厂碾磨车间，地上5层，层高4m，每层局部设置自动喷水灭火系统时可以划分为一个防火分区，其中每层未设置自动喷水灭火系统的建筑面积为1000m2，则每层设置自动喷水灭火系统的建筑面积最大允许为（ ）m2。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1000",false,{"key":16,"text":17,"correct":14},"B","2000",{"key":19,"text":20,"correct":14},"C","3000",{"key":22,"text":23,"correct":24},"D","4000",true,"根据《建筑设计防火规范》GB50016—2014（2018年版）表3．3．1，二级耐火等级的多层乙类厂房，每个防火分区的最大允许建筑面积不应大于3000m2，根据3．3．3，厂房内局部设置自动灭火系统时，其防火分区的增加面积可按该局部面积的1．0倍计算，设置自动喷水灭火系统的建筑面积最大允许为2000×2=4000m2。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]