[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932711":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932711,604,1,"单选题","某二级耐火等级高层乙类厂房，4层，每层建筑面积3900m2，室内净空高度6．5m。该厂房至少应设（ ）个防烟分区。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","6",false,{"key":16,"text":17,"correct":14},"B","16",{"key":19,"text":20,"correct":21},"C","8",true,{"key":23,"text":24,"correct":14},"D","4","根据《建筑设计防火规范》GB50016—2014（2018年版）3．3．1，高层二级耐火等级乙类厂房每个防火分区最大允许建筑面积为1500m2。 根据8．3．1—5，高层乙、丙类厂房应设置自动喷水灭火系统。设置自动喷水灭火系统后防火分区面积可增大1．0倍，即3000m2。 因此，每层至少划分为2个防火分区。根据《建筑防烟排烟系统技术标准》GB51251—2017表4．2．4，室内空间净高H>6．0m时，防烟分区最大允许面积为2000m2。 根据4．2．1，防烟分区不应跨越防火分区。因此，一个防火分区对应一个防烟分区，即每层2个，共4层，至少应设2×4=8个防烟分区。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]