[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932707":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932707,604,1,"单选题","某高层综合楼地下部分设有物业服务用房，建筑面积为900m2，划分为一个防火分区时，设置自动喷水灭火系统区域的面积至少为（ ）m2。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","500",false,{"key":16,"text":17,"correct":14},"B","400",{"key":19,"text":20,"correct":21},"C","800",true,{"key":23,"text":24,"correct":14},"D","900","根据《建筑设计防火规范》GB 50016—2014（2018年版）表5．3．1注1，表中规定的防火分区最大允许建筑面积，当建筑内设置自动灭火系统时，可按本表的规定增加1．0倍；局部设置时，防火分区的增加面积可按该局部面积的1．0倍计算，地下建筑防火分区最大面积为500m2，全部设置自动喷水灭火系统时为1000m2； 设自喷面积为X,没有自喷的为900-X,地下室防火分区面积为500，自喷后为1000，1\u002F2X+（900-X）=500，计算得X=800㎡。面积为400m2设置自动喷水灭火系统，局部翻倍为800m2，未设置自动喷水灭火系统的面积为100m2，共900m2，至少800m2设置自动喷水灭火系统。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]