[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932703":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932703,604,1,"单选题","某一级耐火等级商业综合楼，建筑高度为58m，每层建筑面积12000m2，一至三层为商场，采用不燃材料装修，四层及以上为办公楼，综合楼设置有相应的消防设施，则该商场每层至少应划分（ ）个防火分区。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1",false,{"key":16,"text":17,"correct":14},"B","2",{"key":19,"text":20,"correct":21},"C","3",true,{"key":23,"text":24,"correct":14},"D","4","根据《建筑设计防火规范》GB 50016—2014（2018年版）8．4．1和8．3．3，一类高层公共建筑应设置火灾自动报警系统和自动灭火系统，根据5．3．4，一、二级耐火等级建筑内的商店营业厅、展览厅，当设置自动灭火系统和火灾自动报警系统并采用不燃或难燃装修材料时，其每个防火分区的最大允许建筑面积应符合下列规定：设置在高层建筑内时，不应大于4000m2；设置在单层建筑或仅设置在多层建筑的首层内时，不应大于10000m2；设置在地下或半地下时，不应大于2000m2。该建筑为一类高层公共建筑，根据题意，商场每层的防火分区最大允许面积不应大于4000m2，12000÷4000=3个。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]