[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932696":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932696,604,2,"多选题","建筑的防火墙防止火灾蔓延至相邻区域且耐火极限不低于3．00h的不燃性墙体，防火墙不宜设置在转角处，确需设置时，下列设置符合规范要求的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","内转角两侧墙上的门、窗、洞口之间最近边缘的水平距离为3．0m",false,{"key":16,"text":17,"correct":18},"B","内转角两侧墙上的门、窗、洞口之间最近边缘的水平距离为4．0m",true,{"key":20,"text":21,"correct":18},"C","内转角两侧墙上的门、窗、洞口之间最近边缘的水平距离为5．0m",{"key":23,"text":24,"correct":18},"D","内转角两侧墙上为乙级防火窗时，距离为4m",{"key":26,"text":27,"correct":18},"E","内转角两侧墙上为乙级防火窗时，距离为2m","BCDE","防火墙不宜设置在转角处，确需设置时，内转角两侧墙上的门、窗、洞口之间最近边缘的水平距离不应小于4．0m。采取设置乙级防火窗等防止火灾水平蔓延的措施时，该距离不限。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]