[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932687":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932687,604,1,"单选题","某高层商场外墙采用玻璃幕墙，1-5层设有中庭，消防设施符合国家规定最低标准，下列建筑防火设计符合要求的是（）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","中庭四周采用防火卷帘加水幕冷却保护的分隔方式，耐火极限不小于3.0h",true,{"key":16,"text":17,"correct":18},"B","中庭设有自动喷水灭火系统和火灾自动报警系统，顶面和地面应采用不燃材料装修，设有机械排烟系统",false,{"key":20,"text":21,"correct":18},"C","该建筑每层楼板外檐处未设置实体墙，玻璃幕墙应采用耐火极限不低于1.0h的防火玻璃",{"key":23,"text":24,"correct":18},"D","建筑外墙上、下层开口之间应设置挑出宽度不小于1.2m的防护挑檐","B选项中不要求地面为装修为不燃装修，只要求顶棚墙面为A级材料； 采用防火玻璃墙时，其耐火隔热性和耐火完整性不应低于1.00h，采用耐火完整性不低于1.00h的非隔热性防火玻璃墙时，应设置自动喷水灭火系统保护； 应在每层楼板外沿设置高度不低于1.2 m的实体墙或挑出宽度不小于1.0m长度不小于开口宽度的防火挑檐。 C选项的错误之处在于：只要满足耐火完整性不应低于1.0h即可，不是一定要满足耐火极限不低于1.0h。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]