[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932674":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932674,604,1,"单选题","下列排烟管道的部位，可不设置排烟防火阀的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","垂直风管与每层水平风管交接处的垂直风管上",true,{"key":16,"text":17,"correct":18},"B","排烟风机入口处",false,{"key":20,"text":21,"correct":18},"C","一个排烟系统负担多个防烟分区的排烟支管上",{"key":23,"text":24,"correct":18},"D","穿越防火分区处","根据《建筑防烟排烟系统技术标准》GB51251—20174．4．10，排烟管道下列部位应设置排烟防火阀： 1）垂直风管与每层水平风管交接处的水平管段上。 2）一个排烟系统负担多个防烟分区的排烟支管上。 3）排烟风机入口处。 4）穿越防火分区处。 本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]