[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932672":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932672,604,1,"单选题","下列关于防火阀设置的做法，不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","某27m的公共建筑浴室的竖向排风管，采取防止回流措施，并在支管上设置公称动作温度为70℃的防火阀",false,{"key":16,"text":17,"correct":14},"B","某32m的综合楼卫生间的竖向排风管，采取防止回流措施，并在支管上设置公称动作温度为70℃的防火阀",{"key":19,"text":20,"correct":21},"C","某54m的商业建筑厨房的排油烟管道，采取防止回流措施，并在支管上设置公称动作温度为70℃的防火阀",true,{"key":23,"text":24,"correct":14},"D","排烟防火阀应采用280℃温度熔断器自动关闭","根据《建筑设计防火规范》GB 50016—2014（2018年版）9．3．12，公共建筑的浴室、卫生间和厨房的竖向排风管，应采取防止回流措施并宜在支管上设置公称动作温度为70℃的防火阀，公共建筑内厨房的排油烟管道宜按防火分区设置，且在与竖向排风管连接的支管处应设置公称动作温度为150℃的防火阀；排烟防火阀是安装在排烟系统管道上起隔烟、阻火作用的阀门。它在一定时间内能满足耐火稳定性和耐火完整性的要求，具有手动和自动功能。当管道内的烟气达到280℃时，排烟防火阀自动关闭。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]