[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932669":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932669,604,1,"单选题","建筑内的管道和管道井是火灾烟气和火灾蔓延的途径，下列对建筑内各种井道的说法正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","电缆井墙壁上的检查门采用丙级防火门",true,{"key":16,"text":17,"correct":18},"B","电梯井的井壁耐火极限为1．00h",false,{"key":20,"text":21,"correct":18},"C","建筑内的配电线路通过电梯井敷设",{"key":23,"text":24,"correct":18},"D","管道井在每层用耐火极限为1．00h的不燃材料对缝隙进行封堵","根据《建筑设计防火规范》GB 50016—2014（2018年版）6．2．9—2，电缆井、管道井、排烟道、排气道、垃圾道等竖向井道，应分别独立设置。井壁的耐火极限不应低于1．00h，井壁上的检查门应采用丙级防火门，A选项正确；电梯井的井壁耐火极限应为2．0h，B选项错误；根据6．2．9—1，电梯井应独立设置，井内严禁敷设可燃气体和甲、乙、丙类液体管道，不应敷设与电梯无关的电缆、电线等，C选项错误；根据6．2．9—3，建筑内的电缆井、管道井应在每层楼板处采用不低于楼板耐火极限的不燃材料或防火封堵材料封堵，因此D选项采用耐火极限1．00h的不燃材料进行封堵不正确，应该是根据楼板的实际耐火极限进行选择。本题答案为A。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]