[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932660":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932660,604,1,"单选题","某二级耐火等级的多层丙类厂房，其中一个防火分区局部设置了自动灭火系统，设置自动灭火系统的总面积为1000m2，则该防火分区的最大允许建筑面积为（ ）m2。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","4000",false,{"key":16,"text":17,"correct":18},"B","4500",true,{"key":20,"text":21,"correct":14},"C","5000",{"key":23,"text":24,"correct":14},"D","6000","根据《建筑设计防火规范》GB 50016—2014（2018年版）3．3．1，该厂房在未设置自动灭火系统时，防火分区的最大允许建筑面积为4000m2，根据3．3．3，厂房内局部设置自动灭火系统时，其防火分区的增加面积可按该局部面积的1．0倍计算。新增加的面积也应设置自动灭火系统。因此，该防火分区的最大允许建筑面积为4000+1000／2=4500m2。本题答案为B。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]