[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932658":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932658,604,1,"单选题","某单层商店，划分三个防火分区，分别为 A、 B、 C，A与B防火分隔部位宽度为30m，A与C之间防火分隔部位宽度为45m，则A防火分区所用防火卷帘的总宽度不应大于（ ）m。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","10",false,{"key":16,"text":17,"correct":14},"B","20",{"key":19,"text":20,"correct":21},"C","25",true,{"key":23,"text":24,"correct":14},"D","30","根据《建筑设计防火规范》GB 50016—2014（2018年版）6．5．3—1，除中庭外，当防火分隔部位的宽度不大于30m时，防火卷帘的宽度不应大于10m；当防火分隔部位的宽度大于30m时，防火卷帘的宽度不应大于该部位宽度的1／3，且不应大于20m。与B防火分区的防火卷帘最大宽度为10m，与C防火分区的最大宽度为15m，用防火卷帘总的宽度为10+15=25m。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]