[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932645":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932645,604,1,"单选题","某二级耐火等级商场，地上3层，地下1层，每层建筑面积均为6000m2，地下一层为超市和设备用房，则该设备用房的防火分区最大允许建筑面积不应大于（ ）m2。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","500",false,{"key":16,"text":17,"correct":14},"B","1000",{"key":19,"text":20,"correct":14},"C","1500",{"key":22,"text":23,"correct":24},"D","2000",true,"根据《建筑设计防火规范》GB 50016—2014（2018年版）表5．3．1，地下或半地下建筑（室）的设备用房的防火分区最大允许建筑面积不应大于1000m2，该商场需要设置自动喷水灭火系统，当设置自动灭火系统时，防火分区最大允许建筑面积可按规定增加1．0倍。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]