[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932644":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932644,604,1,"单选题","某建筑高度62m的综合楼，设有裙房，裙房与高层建筑主体之间采用防火墙分隔时，裙房的防火分区最大允许建筑面积为（ ）m2。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1500",false,{"key":16,"text":17,"correct":14},"B","2500",{"key":19,"text":20,"correct":14},"C","3000",{"key":22,"text":23,"correct":24},"D","5000",true,"根据《建筑设计防火规范》GB 50016—2014（2018年版）5．3．1注2，裙房与高层主体之间设置防火墙时，裙房的防火分区可按单、多层建筑的要求确定。对于耐火等级为一级的单、多层建筑，每个防火分区的最大允许建筑面积为2500m2。当全部设置自喷时防火分区的建筑面积可增加1．0倍，由于裙房与高层建筑主体是一个整体，为保证安全，除规范对裙房另有规定外，裙房的防火设计要求应与高层建筑主体的一致，如高层建筑主体的耐火等级为一级时，裙房的耐火等级也不应低于一级，防火分区划分、消防设施设置等也要与高层建筑主体一致等。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]