[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932623":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932623,604,1,"单选题","某民用建筑，地上12层，首层为商业服务网点，每个分隔单元180m2，二层及以上为住宅，下列关于该建筑防火设计说法，不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","住宅与商业服务网点之间应采用耐火极限不低于2．00h且无门、窗、洞口的防火隔墙和1．50h的不燃性楼板完全分隔",false,{"key":16,"text":17,"correct":14},"B","住宅部分的疏散楼梯应独立设置",{"key":19,"text":20,"correct":21},"C","每个分隔单元至少设两个安全出口",true,{"key":23,"text":24,"correct":14},"D","每个分隔单元之间应采用耐火极限不低于2．00h且无门、窗、洞口的防火隔墙相互分隔","根据《建筑设计防火规范》GB50016—2014（2018年版）5．4．11，设置商业服务网点的住宅建筑，其居住部分与商业服务网点之间应采用耐火极限不低于2．00h且无门、窗、洞口的防火隔墙和1．50h的不燃性楼板完全分隔，住宅部分和商业服务网点部分的安全出口和疏散楼梯应分别独立设置；商业服务网点中每个分隔单元之间应采用耐火极限不低于2．00h且无门、窗、洞口的防火隔墙相互分隔，当每个分隔单元任一层建筑面积大于200m2时，该层应设置2个安全出口或疏散门。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]