[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932618":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932618,604,1,"单选题","下列有关燃油锅炉房的说法中，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","常（负）压燃油锅炉房可设置在地下二层",false,{"key":16,"text":17,"correct":14},"B","燃油锅炉房与其储油间之间应采用耐火极限不低于3．00h的防火隔墙分隔",{"key":19,"text":20,"correct":21},"C","燃油锅炉房内设置储油间时，其总储存量不应大于5m3",true,{"key":23,"text":24,"correct":14},"D","燃油锅炉房不应与其他设备用房共用通风系统","根据《建筑设计防火规范》GB 50016—2014（2018年版）5．4．12—1，燃油或燃气锅炉房、变压器室应设置在首层或地下一层的靠外墙部位，但常（负）压燃油或燃气锅炉可设置在地下二层或屋顶上，A选项正确； 根据5．4．12—4，锅炉房内设置储油间时，其总储存量不应大于1m3，且储油间应采用耐火极限不低于3．00h的防火隔墙与锅炉间分隔；确需在防火隔墙上设置门时，应采用甲级防火门，B选项正确，C选项错误； 根据5．4．12—10，燃气锅炉房应设置爆炸泄压设施，燃油或燃气锅炉房应设置独立的通风系统，并应符合本规范第9章的规定，D选项正确。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]