[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932617":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932617,604,1,"单选题","某单层油浸变压器室，建筑面积400m2，柱的耐火极限为2．00h，与建筑高度为32m住宅之间的防火间距不应低于（ ）m。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","10",false,{"key":16,"text":17,"correct":14},"B","12",{"key":19,"text":20,"correct":14},"C","20",{"key":22,"text":23,"correct":24},"D","15",true,"根据《建筑设计防火规范》GB 50016—2014（2018年版）3．2．10，一、二级耐火等级单层厂房（仓库）的柱，其耐火极限分别不应低于2．50h和2．00h。根据3．2．6，油浸变压器室、高压配电装置室的耐火等级不应低于二级。根据表5．1．1，该住宅建筑为二类高层住宅建筑。根据表3．4．1，一二级耐火等级单多层丙类厂房与二类高层民用建筑之间的防火间距不应低于15m。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]