[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932602":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932602,604,2,"多选题","柴油发电机房布置在民用建筑内时应符合的规定有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","可以布置在地下三层及以下",false,{"key":16,"text":17,"correct":14},"B","门应采用乙级防火门",{"key":19,"text":20,"correct":21},"C","应设置火灾报警装置",true,{"key":23,"text":24,"correct":21},"D","应采用耐火极限不低于2．00h的防火隔墙与其他部位分隔",{"key":26,"text":27,"correct":21},"E","应设置与柴油发电机容量和建筑规模相适应的灭火设施","CDE","布置在民用建筑内的柴油发电机房应符合下列规定：（1）宜布置在首层或地下一、二层。（2）不应布置在人员密集场所的上一层、下一层或贴邻。（3）应采用耐火极限不低于2．00h的防火隔墙和1．50h的不燃性楼板与其他部位分隔，门应采用甲级防火门。（4）机房内设置储油间时，其总储存量不应大于1m3，储油间应采用耐火极限不低于3．00h的防火隔墙与发电机房分隔；确需在防火隔墙上开门时，应设置甲级防火门。（5）应设置火灾报警装置。（6）应设置与柴油发电机容量和建筑规模相适应的灭火设施，当建筑内其他部位设置自动喷水灭火系统时，机房内应设置自动喷水灭火系统。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]