[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932600":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932600,604,2,"多选题","下列关于工业建筑附属用房的布置，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","空分厂房内设置有一员工休息室，采用耐火极限不低于 3.00h 的防爆墙隔开，且设置有独立的安全出口",false,{"key":16,"text":17,"correct":18},"B","某鱼类加工厂房内设置有办公室，采用耐火极限为 3.00h 的防火隔墙和 1.00h 的楼板与厂房隔开，设置有一个独立的安全出口",true,{"key":20,"text":21,"correct":14},"C","酚醛泡沫塑料仓库内设置的办公室，采用耐火极限为 2.00h 的防火隔墙和 1.00h 的楼板与库房分隔，设置有独立的安全出口",{"key":23,"text":24,"correct":18},"D","锅炉房内的柴油储罐（容积为 4.8m3），设置在单独房间内，该房间采用 耐火极限不低于 3.00h 的防火隔墙和 1.50h 的楼板与其他部位分隔，房间的门采用 甲级防火门",{"key":26,"text":27,"correct":14},"E","汽车装配车间设置有一轮胎仓库，采用耐火极限为 2.00h 的防火隔墙和 1.00h 的楼板与其他部位分隔。","BD","A选项员工休息室不应设在空分厂房内 C选项 应改为采用耐火极限为 2.50h 的防火隔墙和 1.00h 的楼板与库房分隔， E选项 应改为 采用防火墙和 1.50h 的楼板与其他部位分隔。所以此题答案为BD",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]