[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932597":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932597,604,2,"多选题","下列关于防火间距确定原则的说法，错误的是（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","防火间距应按相邻建筑物外墙的最近距离计算，如外墙有凸出的不燃构件，则应从其凸出部分外缘算起",true,{"key":16,"text":17,"correct":14},"B","变压器之间的防火间距应为相邻变压器内壁的最近水平距离",{"key":19,"text":20,"correct":14},"C","储罐之间的防火间距应为相邻两储罐内壁的最近水平距离",{"key":22,"text":23,"correct":24},"D","堆场之间的防火间距应为两堆场中相邻堆垛外缘的最近水平距离",false,{"key":26,"text":27,"correct":24},"E","建筑物与堆场的防火间距，应为建筑外墙至堆场中相邻堆垛外缘的最近水平距离","ABC","根据《建筑设计防火规范》GB50016—2014（2018版）B．0．1，建筑物之间的防火间距应按相邻建筑外墙的最近水平距离计算，当外墙有凸出的可燃或难燃构件时，应从其凸出部分外缘算起，建筑物与储罐、堆场的防火间距，应为建筑外墙至储罐外壁或堆场中相邻堆垛外缘的最近水平距离，A选项错误，E选项正确；根据B．0．4，变压器之间的防火间距应为相邻变压器外壁的最近水平距离，B选项错误；根据B．0．2，储罐之间的防火间距应为相邻两储罐外壁的最近水平距离，C选项错误；根据B．0．3，堆场之间的防火间距应为两堆场中相邻堆垛外缘的最近水平距离，D选项正确。本题答案为ABC。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]