[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932593":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932593,604,2,"多选题","下列设备用房，设置在民用建筑地下或半地下时，疏散门应直通室外或安全出口的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","柴油发电机房",false,{"key":16,"text":17,"correct":18},"B","消防控制室",true,{"key":20,"text":21,"correct":18},"C","消防水泵房",{"key":23,"text":24,"correct":18},"D","燃油锅炉房",{"key":26,"text":27,"correct":18},"E","油浸变压器室","BCDE","根据《建筑设计防火规范》GB 50016—2014（2018年版）5．4．12—1，常压或负压的燃油燃气锅炉房、变压器室燃油或燃气锅炉房、变压器室应设置在首层或地下一层的靠外墙部位，根据5．4．12—2，锅炉房、变压器室的疏散门均应直通室外或安全出口，E选项正确，D选项正确；根据8．1．6，消防水泵房的疏散门应直通室外或安全出口，C选项正确：根据8．1．7，消防控制室的疏散门应直通室外或安全出口，B选项正确。本题答案为BCDE。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]