[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932591":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932591,604,2,"多选题","某二级耐火等级的多层大豆油精炼车间，其周边布置有多座二级耐火等级建筑，下列关于该车间与周边建筑物防火间距的做法中，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","与油浸变压器室（建筑高度7m）的防火间距为10m",true,{"key":16,"text":17,"correct":18},"B","与陶瓷制品烘干厂（建筑高度26m）的防火间距为12m",false,{"key":20,"text":21,"correct":14},"C","与大豆油原料仓库（建筑高度15m）的防火间距为13m",{"key":23,"text":24,"correct":14},"D","与大豆油成品仓库（建筑高度21m）的防火间距为16m",{"key":26,"text":27,"correct":18},"E","与大豆油浸出车间（建筑高度6m）的防火间距为10m","ACD","根据《建筑设计防火规范》GB 50016—2014（2018年版）3．1．1、3．1．3条文说明，大豆油精炼车间的火灾危险性为丙类、油浸变压器室的火灾危险性为丙类、陶瓷制品烘干厂的火灾危险性为丁类、大豆油原料仓库的火灾危险性为丙类、大豆油成品仓库的火灾危险性为丙类、大豆油浸出车间的火灾危险性为甲类。根据表3．4．1，A选项之间的防火间距不应小于10m；B选项之间的防火间距不应小于13m；C选项之间的防火间距不应小于10m；D选项之间的防火间距不应小于10m；E选项之间的防火间距不应小于12m。本题答案为ACD。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]