[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932586":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932586,604,1,"单选题","下列符合建筑平面布置规范要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","锅炉房、变压器室与其他部位之间采用耐火极限为2．00h的防火隔墙和1．00h的不燃性楼板隔开",false,{"key":16,"text":17,"correct":18},"B","单独建造的消防控制室其耐火等级为二级",true,{"key":20,"text":21,"correct":14},"C","柴油发电机房布置在某商场的地下一层",{"key":23,"text":24,"correct":14},"D","电影院观影厅布置在某商场6层，建筑面积为400m2并设置了1个疏散门","锅炉房、变压器室与其他部位之间应采用耐火极限不低于2．00h的防火隔墙和1．5h的不燃性楼板隔开。柴油发电机房不应布置在人员密集场所的上一层、下一层或贴邻。电影院设置在一、二级耐火等级的建筑内时，观众厅宜布置在首层、二层或三层；确需布置在四层及以上楼层时，一个厅、室的疏散门不应少于2个，且每个观众厅的建筑面积不宜大于400m2。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]