[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932585":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932585,604,1,"单选题","下列关于柴油发电机房的布置说法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","布置在办公楼的地下一层",false,{"key":16,"text":17,"correct":18},"B","布置在地下商场旁边",true,{"key":20,"text":21,"correct":14},"C","布置在医院的地下二层",{"key":23,"text":24,"correct":14},"D","机房内设置储油间时，其总储存量不应大于1m3","柴油发电机房布置在民用建筑内时应符合下列规定：（1）宜布置在建筑物的首层及地下一、二层，不应布置在人员密集场所的上一层、下一层或贴邻。（2）应采用耐火极限不低于2．00h的防火隔隔墙和耐火极限不低于1．50h的不燃性楼板与其他部位隔开，门应采用甲级防火门。（3）机房内设置储油间时，其总储存量不应大于1m3，储油间应采用耐火极限不低于3．00h的防火隔墙与发电机房分隔；当必须在防火隔墙上开门时，应设置甲级防火门。（4）应设置火灾报警装置。（5）应设置与柴油发电机容量和建筑规模相适应的灭火设施，当建筑内其他部位设置自动喷水灭火系统时，机房内应设置自动喷水灭火系统。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]