[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932580":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932580,604,1,"单选题","某建筑高度为24m的丙类厂房，耐火等级为二级，拟在其旁边新建一座5层难燃铝塑材料加工厂房、建筑高度为25m，难燃铝塑材料加工厂房外墙上的门、窗、洞口均采用甲级防火门、窗，则两座厂房之间的防火间距不应小于（）m。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","10",false,{"key":16,"text":17,"correct":14},"B","6",{"key":19,"text":20,"correct":14},"C","13",{"key":22,"text":23,"correct":24},"D","4",true,"难燃铝塑材料加工厂房的生产火灾危险性为丁类，根据《建筑设计防火规范》GB50016—2014（2018版）3．2．2，高层厂房的耐火等级不应低于二级，25m的5层难燃铝塑材料加工厂房的耐火等级不应低于二级，根据表3．4．1注3，两座一、二级耐火等级的厂房，当相邻较低一面外墙为防火墙且较低一座厂房的屋顶无天窗，屋顶的耐火极限不低于1．00h，或相邻较高一面外墙的门、窗等开口部位设置甲级防火门、窗或防火分隔水幕或符合规范规定的防火卷帘时，丙、丁、戊类厂房之间的防火间距不应小于4m。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]